Extinguishes fire by releasing CO₂ into enclosed spaces to reduce oxygen concentration below the combustion threshold — fast, residue-free and non-conductive. Equipped with four-level activation: pneumatic, electric, manual and mechanical emergency. Suitable for international and domestic vessels, warships and offshore oil platforms.
| Technical Parameters | |
|---|---|
| CO₂ Cylinder Volume | 8 ~ 82 L |
| Pilot Cylinder (N₂) Volume | 4 L |
| CO₂ Filling Ratio | ≤ 0.67 kg/L |
| Ambient Temperature | -10°C ~ +50°C |
| Relative Humidity | 93 ± 3% |
| Power Supply | AC220V/380V/440V · DC24V |
| Power Consumption | Standby ≤30W / Active 200W |
| Discharge Delay | Pneumatic 20~40s / Electric 20~40s |
| Pilot Gas | N₂, filling pressure 5.9 MPa |
| Activation | Electric / Pneumatic / Manual / Mechanical Emergency |

Large storage capacity, light weight, compact footprint and short refilling time — ideal for large-volume spaces on car carriers, ro-pax vessels and large container ships. Features intelligent monitoring with real-time parameter display, dual pressure and level alarms, and automatic chiller start/stop.
| Technical Parameters | |
|---|---|
| Model | YN-CO2L-5/30 |
| Working Pressure | 2.0 ± 0.2 MPa |
| Design Pressure | 2.5 MPa |
| Working Temperature | -20°C ~ +50°C |
| Filling Factor | ≤ 95% |
| Power Supply | AC440V/380V 50/60Hz · DC24V |
| Discharge Time | Total flooding ≤1min / Local application ≤7min |
| Activation | Automatic / Manual / Mechanical Emergency |
| Application | Total Flooding, Local Application |

Consists of storage cylinders, selector valves, piping network, nozzles and fire detection control. High extinguishing efficiency, no pollution — suitable for manned spaces such as engine rooms, control rooms and offshore platforms. Available in cabinet-type and rack-type configurations.
| Technical Parameters | |
|---|---|
| Models | ZQC-10/20/30/40/70/90/120/150/180 |
| Cylinder Volume | 10/20/30/40/70/90/120/150/180 L |
| Filling Density | ≤0.95 kg/L (welded) / ≤1.125 kg/L (seamless) |
| Design Concentration | 8.5% |
| Nominal Working Pressure | 2.5 / 4.2 MPa |
| Max Working Pressure | 4.2 / 5.3 MPa |
| Discharge Time | ≤ 10 s |
| Working Temperature | 0 ~ 50°C |
| Nozzle Protection Radius | ≤ 5 m |
| Activation | Pneumatic / Electric / Manual |

A new-generation environmentally friendly clean agent with a GWP of just 1 and an atmospheric lifetime of only 5 days. Leaves no residue after discharge and causes zero damage to precision navigation equipment, electronic systems and machinery — the next-generation replacement for halon and HFC agents.
| Technical Parameters | |
|---|---|
| Cylinder Volume | 10 ~ 150 L |
| Filling Density | ≤0.95 kg/L (welded) / ≤1.12 kg/L (seamless) |
| Design Concentration | 5.9% |
| Working Pressure | 4.2 MPa |
| Working Temperature | 0 ~ 50°C |
| Activation | Electric / Pneumatic / Manual |

Provides inert gas protection for gas carriers and chemical tankers via nitrogen cylinder banks and pressure regulation, preventing flammable atmospheres in cargo holds. Model YND68, equipped with primary/secondary pressure reducing valve groups.
| Technical Parameters | |
|---|---|
| Model | YND68 |
| Medium | Nitrogen (N₂) |
| Components | N₂ cylinder bank, regulation box, primary/secondary reducing valves |

PHYM series with horizontal tank volumes of 0.2~10.0m³ and vertical tank volumes of 0.2~3.0m³. Supplied with air foam proportioners, pressure proportioners, in-line and around-the-pump proportioners at 3%/6% mixing ratios.
| Technical Parameters | |
|---|---|
| Model Series | PHYM |
| Horizontal Tank Volume | 0.2 ~ 10.0 m³ |
| Vertical Tank Volume | 0.2 ~ 3.0 m³ |
| Working Pressure | 0.6 ~ 1.2 MPa |
| Solution Flow Rate | 4 ~ 200 L/s (by proportioner type) |
| Mixing Ratio | 3% / 6% |
| Pressure Loss | ≤ 0.2 MPa (pressure type) / ≤ 0.4 MPa (in-line) |

PHP series with solution flow rates of 8~600 L/s, suitable for large oil tankers, chemical carriers, helidecks and offshore platforms. Tank volume calculated at 100× the model suffix (e.g. PHP32-15 = 1,500L).
| Technical Parameters | |
|---|---|
| Model Series | PHP32 ~ PHP600-X |
| Solution Flow Rate | 8 ~ 260 L/s (PHP600-X: 600m³/h) |
| Working Pressure | 0.6 ~ 1.2 MPa (PHP600-X: 1.4 MPa) |
| Working Temperature | 0 ~ 45°C |
| Mixing Ratio | 3% / 6% |
| Tank Volume | 100△ L (△ = model suffix × 100) |
| Inlet/Outlet Pressure Differential | ≤ 0.2 MPa |

PF1 foam generator with expansion ratio ≥300:1, foam supply rate of 30m³/min and minimum design filling rate of 1.2m/min. Uses an internal air aspiration system for machinery spaces, cargo pump rooms, vehicle spaces, ro-ro spaces and special category spaces.
| Technical Parameters (PF1 Generator) | |
|---|---|
| Model | PF1 |
| Expansion Ratio | ≥ 300:1 |
| Rated Working Pressure | 0.6 MPa |
| Working Pressure Range | 0.6 ~ 1.2 MPa |
| Rated Flow Rate | 1 L/s |
| Mixing Ratio | 3% |
| 50% Drainage Time | ≥ 10 min |
| Foam Supply Rate | 30 m³/min |
| Min Design Filling Rate | 1.2 m/min |
| System Type | Internal air aspiration system |

FPC series with powder tank volumes of 200~10,000L, nitrogen-driven, equipped with electric/manual powder monitors, powder hand hoses and reel cabinets. Monitor range 18~50m, hand hose range ≥12m. Effective against flammable gas and liquid jet fires.
| Technical Parameters | |
|---|---|
| Model Range | FPC-(200~10000) |
| Powder Tank Volume | 200 ~ 10000 L |
| Working Pressure | 1.0 ~ 1.5 MPa |
| Propellant Gas | N₂ |
| Hand Hose Discharge Rate | FQ3.5 / 3.5 kg/s · FQ5 / 5 kg/s |
| Hand Hose Range | ≥ 12 m |
| Monitor Discharge Rate | 11/25/35/40/45/50 kg/s |
| Monitor Range | ≥ 18/30/38/40/45/50 m |

Available in medium-high pressure and low pressure versions for local fire fighting in Category A machinery spaces. No space sealing required, no personnel evacuation needed — can discharge while engines are running. Medium-high pressure nozzles in QA19-2 material.
| Technical Parameters | |
|---|---|
| System Type | Medium-High Pressure / Low Pressure |
| Spray Cone Angle | 120° |
| Nozzle Material | QA19-2 |
| Extinguishing Method | Local application, no sealing required |

Wet automatic sprinkler system consisting of wet alarm valves, pressure water tanks, sprinkler pumps, make-up pumps, water flow indicators, safety signal butterfly valves and sprinkler heads. ZSFZ series wet alarm valves in nominal diameters DN80~DN150.
| Technical Parameters (ZSFZ Wet Alarm Valve) | |
|---|---|
| ZSFZ80 | DN80, 1.2MPa, delay 15~60s |
| ZSFZ100 | DN100, 1.2MPa |
| ZSFZ150 | DN150, 1.2MPa |

Fixed pressure water mist system for ship machinery spaces and cargo pump rooms, consisting of diesel fire pumps, pressure water tanks and water mist nozzles. Maximum nozzle distance from bulkhead ≤1.2m, 0.65m above tank top.
| Technical Parameters | |
|---|---|
| Nozzle Height Above Tank Top | 0.65 m |
| Max Distance from Bulkhead | ≤ 1.2 m (alt. spec. ≤1.7m) |
| Max Enclosed Space Volume | 3000 m³ |
| System Components | Diesel pump, pressure water tank, mist nozzles |

Designed specifically for vehicle ro-ro spaces and special category spaces. Nozzles in HPb59-1 material, installation height ≤9m, maximum horizontal spacing 3.0m×3.0m, distance below ceiling ≤0.6m.
| Technical Parameters | |
|---|---|
| Nozzle Material | HPb59-1 |
| Installation Height | ≤ 9 m |
| Max Horizontal Spacing | 3.0 m × 3.0 m |
| Distance Below Ceiling | ≤ 0.6 m |
| System Components | Water mist pump, pump control cabinet, mist nozzles |

Flow rates 24~100 L/s, water throw 55~90m, foam throw 42~85m, 360° horizontal rotation, elevation -30°~+60°, expansion ratio ≥6, 25% drainage time ≥2.5min.
| Model | Flow (L/s) | Water Throw (m) | Foam Throw (m) | Rated Pressure |
|---|---|---|---|---|
| 24 | 24 | ≥55 | ≥42 | 0.8 MPa |
| 32 | 32 | ≥60 | ≥48 | 0.8 MPa |
| 40 | 40 | ≥65 | ≥55 | 0.8 MPa |
| 48 | 48 | ≥70 | ≥60 | 1.0 MPa |
| 64 | 64 | ≥75 | ≥70 | 1.0 MPa |
| 80 | 80 | ≥85 | ≥80 | 1.2 MPa |
| 100 | 100 | ≥90 | ≥85 | 1.2 MPa |


PSKDC series electric-controlled water monitors with flow rates 720~1,200m³/h and water throw 120~160m; PLKDC series foam-water dual monitors with water throw ≥120m and foam throw ≥110m/≥70m. 300° horizontal rotation, elevation -30°~+70°, remote control distance ≤150m.
| Technical Parameters (PSKDC Water Monitor) | |
|---|---|
| PSKDC1200 | 1,200m³/h, water throw ≥160m |
| PSKDC900 | 900m³/h, water throw ≥140m |
| PSKDC720 | 720m³/h, water throw ≥120m |
| Rated Working Pressure | 1.2 MPa (range 0.4~1.6 MPa) |
| Horizontal / Elevation | 300° / -30°~+70° |
| Power / Motor | AC380V 50Hz + DC24V; horizontal 1.1kW / elevation 2.2kW |
| Remote Control Distance | ≤ 150 m |
| Connection | Flange DN200 1.6MPa |

CXB series diesel engine-driven fire pumps with flow rates of 300~1,500m³/h, head of 140m and speed of 1,800rpm. Depending on engine speed variation, maximum flow can exceed 2,400m³/h and maximum head can exceed 160m.
| Pump Model | Flow (m³/h) | Head (m) | Shaft Power (kW) | Engine Power (kW) |
|---|---|---|---|---|
| 350CXB300-565 | 1500 | 140 | 715 | 850 |
| 350CXB300-565(A) | 1200 | 140 | 587 | 700 |
| 300CXB250-565 | 1000 | 140 | 496 | 600 |
| 350CXB250-565(A) | 800 | 140 | 410 | 500 |
| 250CXB200-565 | 600 | 140 | 314 | 400 |
| 200CXB150-565 | 400 | 140 | 218 | 275 |
| 200CXB150-565(A) | 300 | 140 | 164 | 200 |



TP series monitor towers at heights of 8~20m; PQ8 series air foam branches at 0.5MPa working pressure and 8L/s solution flow; SJP16 water/foam hose stations for oil platforms, ships and terminals.
| Fire Monitor Tower | |
|---|---|
| Models | TP8 / TP10 / TP12 / TP16 / TP18 / TP20 |
| Upper Platform Height | 8 / 10 / 12 / 16 / 18 / 20 m |
| Platform Spacing | 2.5 m (with intermediate/lower platforms) |
| Water Curtain Consumption | ≥ 6 L/s |

Full range of fire alarm control panels (recessed/wall-mounted), fire repeaters, smoke detectors, heat detectors, flame detectors, manual call points, sounder beacons, remote control boxes and pump control cabinets — fully integrable with all suppression systems.
| Main Products | |
|---|---|
| Fire Alarm Control Panel | Recessed / Wall-mounted |
| Fire Repeater Panel | Recessed / Wall-mounted |
| Detectors | Smoke, Heat, Flame detectors |
| Alarm Devices | Manual call points, sounder beacons, bells |
| Control Equipment | Remote control boxes, pump control cabinets, fire control units |
| System Accessories | Medium-high/low pressure mist nozzles, cylinder valves, discharge valves, selector valves |
Provide your vessel type, space parameters and classification society requirements — our engineers will configure the optimal fire system solution
Submit Your Inquiry